24 CFR 3280.509
§ 3280.509 Criteria in absence of specific data.
United States · 24 CFR — Housing and Urban Development · Status: effective
Cite this
- Citation
- 24 CFR 3280.509, § 3280.509 Criteria in absence of specific data, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/102969
- Permanent ID
ys:prov:102969@1- SHA-256
a13cdab0a71309749a8725c82059a2f847b1b81d8827308e27f1cfafe632c46b
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
In the absence of specific data, for purposes of heat-loss/gain calculation, the following criteria shall be used:
(a) Infiltration heat loss. In the absence of measured infiltration heat loss data, the following formula shall be used to calculate heat loss due to infiltration and intermittently operated fans exhausting to the outdoors. The perimeter calculation shall be based on the dimensions of the pressure envelope.
(b) Framing areas.
(c) Insulation compression. Insulation compressed to less than nominal thickness and loose-fill insulation in sloping cavities must have its nominal R-values reduced in compressed areas in accordance with the following table:
Table to Paragraph (c)—Effect of Insulation Compression and Restriction on R-Values
(d) Air supply ducts within floor cavity. Air supply ducts located within a floor cavity shall be assumed to be heating or cooling the floor cavity to living space temperatures unless the duct is structurally isolated by the framing system or thermally insulated from the rest of the floor cavity with a thermal insulation at least equal to R-4.
(e) Air supply ducts within ceiling cavity. Where supply ducts are located in ceiling cavities, the influence of the duct on cavity temperatures shall be considered in calculating envelope heat loss or heat gain.
(f) The supply duct loss (and/or heat gain where applicable—See § 3280.511) shall be calculated using the actual duct surface area and the actual thickness of insulation between the duct and outside of the manufactured home. If there is an air space of at least 1/2 inch between the duct and the insulation, heat loss/gain need not be calculated if the cavity in which the duct is located is assumed to be at living space temperature. The average temperature inside the supply duct, including ducts installed outside the manufactured home, shall be assumed to be 130 F for purposes of calculation of heat loss and 60 F for heat gain.
(g) Return air cavities. Cavities used as return air plenums shall be considered to be at living space temperature.
Legislative history
This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.