24 CFR 3285.204
§ 3285.204 Ground moisture control.
United States · 24 CFR — Housing and Urban Development · Status: effective
Cite this
- Citation
- 24 CFR 3285.204, § 3285.204 Ground moisture control, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/103174
- Permanent ID
ys:prov:103174@1- SHA-256
645f1687277c61c587a99fe8a35443d2eeb5fc659cd2f7fbc30f7b464305f403
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) Vapor retarder. If the space under the home is to be enclosed with skirting or other materials, a vapor retarder must be installed to cover the ground under the home, unless the home is installed in an arid region with dry soil conditions.
(b) Vapor retarder material. A minimum of six mil polyethylene sheeting or its equivalent must be used.
(c) Proper installation.
(1) The entire area under the home must be covered with the vapor retarder, as noted in § 3285.204(a), except for areas under open porches, decks, and recessed entries. Joints in the vapor retarder must be overlapped at least 12 inches.
(2) The vapor retarder may be placed directly beneath footings, or otherwise installed around or over footings placed at grade, and around anchors or other obstructions.
(3) Any voids or tears in the vapor retarder must be repaired. At least one repair method must be provided in the manufacturer's installation instructions.
Legislative history
This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.