24 CFR 3285.306

§ 3285.306 Design procedures for concrete block piers.

United States · 24 CFR — Housing and Urban Development · Status: effective

Get this as JSONEmbed this
Cite this
Citation
24 CFR 3285.306, § 3285.306 Design procedures for concrete block piers, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/103181
Permanent ID
ys:prov:103181@1
SHA-256
13016543cd4d3c261fbcbd779a97ae727a75320f46b9853a54d6ceab26aa438b

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) Frame piers less than 36 inches high. (1) Frame piers less than 36 inches high are permitted to be constructed of single, open, or closed-cell concrete blocks, 8 inches “ 8 inches “ 16 inches, when the design capacity of the block is not exceeded. (2) The frame piers must be installed so that the long sides are at right angles to the supported I-beam, as shown in Figure A to this section. (3) The concrete blocks must be stacked with their hollow cells aligned vertically and must be positioned at right angles to the footings. (4) Horizontal offsets from the top to the bottom of the pier must not exceed one-half inch. (5) Mortar is not required, unless specified in the installation instructions or required by a registered professional engineer or registered architect. (b) Frame piers 36 inches to 67 inches high and corner piers. (1) All frame piers between 36 inches and 67 inches high and all corner piers over three blocks high must be constructed out of double, interlocked concrete blocks, as shown in Figure B to this section, when the design capacity of the block is not exceeded. Mortar is not required for concrete block piers, unless otherwise specified in the installation instructions or required by a professional engineer or registered architect. (2) Horizontal offsets from the top to the bottom of the pier must not exceed one inch. (c) All piers over 67 inches high. Piers over 67 inches high must be designed by a registered professional engineer or registered architect, in accordance with acceptable engineering practice. Mortar is not required for concrete block piers, unless otherwise specified in the manufacturer installation instructions or by the design.

Legislative history

This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.