24 CFR 3285.311
§ 3285.311 Required perimeter supports.
United States · 24 CFR — Housing and Urban Development · Status: effective
Cite this
- Citation
- 24 CFR 3285.311, § 3285.311 Required perimeter supports, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/103186
- Permanent ID
ys:prov:103186@1- SHA-256
fd868cff45ce48abd5de1b14aae133f7a5f09575378b994d7c055d7f9371e943
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) Perimeter pier or other supports must be located as follows:
(1) On both sides of side wall exterior doors (such as entry, patio, and sliding glass doors) and any other side wall openings of 48 inches or greater in width, and under load-bearing porch posts, factory installed fireplaces, and fireplace stoves).
(2) Other perimeter supports must be:
(i) Located in accordance with Table 2 to § 3285.303; or
(ii) Provided by other means such as additional outriggers or floor joists. When this alternative is used, the designs required by § 3285.301 must consider the additional loads in sizing the pier and footing supports under the main chassis beam.
(b) For roof live loads of 40 psf or greater, a professional engineer or architect must determine the maximum sidewall opening permitted without perimeter pier or other supports.
(c) The location and installation of any perimeter pier support must not take the home out of compliance with the Manufactured Home Construction and Safety Standards (part 3280 of this chapter).