§ 3285.804 Bottom board repair.

United States · 24 CFR — Housing and Urban Development · Status: effective

Get this as JSONEmbed this
Cite this
Citation
24 CFR 3285.804, § 3285.804 Bottom board repair, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/103221
Permanent ID
ys:prov:103221@1
SHA-256
f30d3ba99962e2dafedbd639f9714c3c504789fd5309aaecb5304e8189320603

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) The bottom board covering must be inspected for any loosening or areas that might have been damaged or torn during installation or transportation. Any missing insulation is to be replaced prior to closure and repair of the bottom board. (b) Any splits or tears in the bottom board must be resealed with tape or patches in accordance with methods provided in the manufacturers installation instructions. (c) Plumbing P-traps must be checked to be sure they are well-insulated and covered. (d) All edges of repaired areas must be taped or otherwise sealed.