29 CFR 1926.958
§ 1926.958 Materials handling and storage.
United States · 29 CFR — Labor · Status: effective
Cite this
- Citation
- 29 CFR 1926.958, § 1926.958 Materials handling and storage, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/129363
- Permanent ID
ys:prov:129363@1- SHA-256
d65e3049fed3c3fb0594698239b133e60c117ade040ed028f5d79791a470d122
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) General. Materials handling and storage shall comply with applicable material-handling and material-storage requirements in this part, including those in subparts N and CC of this part.
(b) Materials storage near energized lines or equipment—(1) Unrestricted areas. In areas to which access is not restricted to qualified persons only, materials or equipment may not be stored closer to energized lines or exposed energized parts of equipment than the following distances, plus a distance that provides for the maximum sag and side swing of all conductors and for the height and movement of material-handling equipment:
(i) For lines and equipment energized at 50 kilovolts or less, the distance is 3.05 meters (10 feet).
(ii) For lines and equipment energized at more than 50 kilovolts, the distance is 3.05 meters (10 feet) plus 0.10 meter (4 inches) for every 10 kilovolts over 50 kilovolts.
(2) Restricted areas. In areas restricted to qualified employees, materials may not be stored within the working space about energized lines or equipment.
Paragraph (b) of § 1926.966 specifies the size of the working space.
Legislative history
This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.