yourstate.us
30 CFR 75.521

§ 75.521 Lightning arresters; ungrounded and exposed power conductors and telephone wires.

United States · 30 CFR — Mineral Resources · Status: effective

Get this as JSONEmbed this
Cite this
Citation
30 CFR 75.521, § 75.521 Lightning arresters; ungrounded and exposed power conductors and telephone wires, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/133589
Permanent ID
ys:prov:133589@1
SHA-256
2d49526a1905c969da536feaa678c22ac68786015b6cb363f65b5da4c9d3adef

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

Each ungrounded, exposed power conductor and each ungrounded, exposed telephone wire that leads underground shall be equipped with suitable lightning arresters of approved type within 100 feet of the point where the circuit enters the mine. Lightning arresters shall be connected to a low resistance grounding medium on the surface which shall be separated from neutral grounds by a distance of not less than 25 feet.

Legislative history

This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.