yourstate.us
30 CFR 75.800-3

§ 75.800-3 Testing, examination and maintenance of circuit breakers; procedures.

United States · 30 CFR — Mineral Resources · Status: effective

Get this as JSONEmbed this
Cite this
Citation
30 CFR 75.800-3, § 75.800-3 Testing, examination and maintenance of circuit breakers; procedures, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/133646
Permanent ID
ys:prov:133646@1
SHA-256
914a36bc39aebff10939dd5eeba41db6a09be36ac98eeb7685a9f34e4eae3eed

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) Circuit breakers and their auxiliary devices protecting underground high-voltage circuits shall be tested and examined at least once each month by a person qualified as provided in § 75.153; (b) Tests shall include: (1) Breaking continuity of the ground check conductor, where ground check monitoring is used; and (2) Actuating at least two (2) of the auxiliary protective relays. (c) Examination shall include visual observation of all components of the circuit breaker and its auxiliary devices, and such repairs or adjustments as are indicated by such tests and examinations shall be carried out immediately.

Legislative history

This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.