§ 75.801 Grounding resistors.
United States · 30 CFR — Mineral Resources · Status: effective
Cite this
- Citation
- 30 CFR 75.801, § 75.801 Grounding resistors, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/133648
- Permanent ID
ys:prov:133648@1- SHA-256
b6d0fb1f94d77f4d3ac7aebf4119aafc1a23aa5b66b654076ccb994e3aadf579
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
The grounding resistor, where required, shall be of the proper ohmic value to limit the voltage drop in the grounding circuit external to the resistor to not more than 100 volts under fault conditions. The grounding resistor shall be rated for maximum fault current continuously and insulated from ground for a voltage equal to the phase-to-phase voltage of the system.