§ 75.907 Design of trailing cables for medium-voltage circuits.

United States · 30 CFR — Mineral Resources · Status: effective

Get this as JSONEmbed this
Cite this
Citation
30 CFR 75.907, § 75.907 Design of trailing cables for medium-voltage circuits, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/133702
Permanent ID
ys:prov:133702@1
SHA-256
bb6e0f05515d0ffda646d96db629d061a5a50ed8b9a180ff05d121c50da5cad1

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

Trailing cables for medium-voltage circuits shall include grounding conductors, a ground check conductor, and grounded metallic shields around each power conductor or a ground metallic shield over the assembly, except that on equipment employing cable reels, cables without shields may be used if the insulation is rated 2,000 volts or more.