30 CFR 75.1001-1
§ 75.1001-1 Devices for overcurrent protection; testing and calibration requirements; records.
United States · 30 CFR — Mineral Resources · Status: effective
Cite this
- Citation
- 30 CFR 75.1001-1, § 75.1001-1 Devices for overcurrent protection; testing and calibration requirements; records, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/133707
- Permanent ID
ys:prov:133707@1- SHA-256
e4e961ae89f021bc2921b0d9703b9b189dc1ca79e00f354a89da55848a84d51f
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) Automatic circuit interrupting devices that will deenergize the affected circuit upon occurrence of a short circuit at any point in the system will meet the requirements of § 75.1001.
(b) Automatic circuit interrupting devices described in paragraph (a) of this section shall be tested and calibrated at intervals not to exceed six months. Testing of such devices shall include passing the necessary amount of electric current through the device to cause activation. Calibration of such devices shall include adjustment of all associated relays to ±15 percent of the indicated value. An authorized representative of the Secretary may require additional testing or calibration of these devices.
(c) A record of the tests and calibrations required by paragraph (b) of this section shall be kept, and shall be made available, upon request, to an authorized representative of the Secretary.