yourstate.us
30 CFR 77.509

§ 77.509 Transformers; installation and guarding.

United States · 30 CFR — Mineral Resources · Status: effective

Get this as JSONEmbed this
Cite this
Citation
30 CFR 77.509, § 77.509 Transformers; installation and guarding, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/134052
Permanent ID
ys:prov:134052@1
SHA-256
800d21ff80d779cb51c72d82f11d1c19c1acb3b9a1b7e38a0be793bc889693bb

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) Transformers shall be of the totally enclosed type, or shall be placed at least 8 feet above the ground, or installed in a transformer house, or surrounded by a substantial fence at least 6 feet high and at least 3 feet from any energized parts, casings, or wiring. (b) Transformer stations shall be enclosed to prevent persons from unintentionally or inadvertently contacting energized parts. (c) Transformer enclosures shall be kept locked against unauthorized entry.

Legislative history

This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.