yourstate.us
30 CFR 77.701-3

§ 77.701-3 Grounding wires; capacity.

United States · 30 CFR — Mineral Resources · Status: effective

Get this as JSONEmbed this
Cite this
Citation
30 CFR 77.701-3, § 77.701-3 Grounding wires; capacity, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/134075
Permanent ID
ys:prov:134075@1
SHA-256
11fab021facecbfbc3ad6d88654b0a8ef73cd79511f7dfa678271d1cdc1d6436

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

Where grounding wires are used to ground metallic sheaths, armors, conduits, frames, casings, and other metallic enclosures, such grounding wires will be approved if: (a) Where the power conductor used is No. 6 A.W.G., or larger, the cross-sectional area of the grounding wire is at least one-half the cross-sectional area of the power conductor. (b) Where the power conductor used is less than No. 6 A.W.G., the cross-sectional area of the grounding wire is equal to the cross-sectional area of the power conductor.

Legislative history

This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.