§ 77.800-1 Testing, examination, and maintenance of circuit breakers; procedures.

United States · 30 CFR — Mineral Resources · Status: effective

Get this as JSONEmbed this
Cite this
Citation
30 CFR 77.800-1, § 77.800-1 Testing, examination, and maintenance of circuit breakers; procedures, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/134095
Permanent ID
ys:prov:134095@1
SHA-256
d5adf4d783e75bb4ffa878d0c54a91288cac875f8728c2138216440fd68be37e

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) Circuit breakers and their auxiliary devices protecting high-voltage circuits to portable or mobile equipment shall be tested and examined at least once each month by a person qualified as provided in § 77.103. (b) Tests shall include: (1) Breaking continuity of the ground check conductor where ground check monitoring is used; and, (2) Actuating any of the auxiliary protective relays. (c) Examination shall include visual observation of all components of the circuit breaker and its auxiliary devices, and such repairs or adjustments as are indicated by such tests and examinations shall be carried out immediately.