§ 77.803 Fail safe ground check circuits on high-voltage resistance grounded systems.

United States · 30 CFR — Mineral Resources · Status: effective

Get this as JSONEmbed this
Cite this
Citation
30 CFR 77.803, § 77.803 Fail safe ground check circuits on high-voltage resistance grounded systems, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/134100
Permanent ID
ys:prov:134100@1
SHA-256
0c1967ba18a0e08e14338ebfdc02d0bf5432d57d7cd09cfa32bc1c4664e1178e

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

On and after September 30, 1971, all high-voltage, resistance grounded systems shall include a fail safe ground check circuit or other no less effective device approved by the Secretary to monitor continuously the grounding circuit to assure continuity. The fail safe ground check circuit shall cause the circuit breaker to open when either the ground or ground check wire is broken.