§ 77.804 High-voltage trailing cables; minimum design requirements.
United States · 30 CFR — Mineral Resources · Status: effective
Cite this
- Citation
- 30 CFR 77.804, § 77.804 High-voltage trailing cables; minimum design requirements, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/134103
- Permanent ID
ys:prov:134103@1- SHA-256
dc7c3709feba7e85d6435c51d1e078527c8a3947a6a41049565636329587e1aa
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) High-voltage trailing cables used in resistance grounded systems shall be equipped with metallic shields around each power conductor with one or more ground conductors having a total cross-sectional area of not less than one-half the power conductor, and with an insulated conductor for the ground continuity check circuit. External ground check conductors may be used if they are not smaller than No. 8 (AWG) and have an insulation rated at least 600 volts.
(b) All such high-voltage trailing cables shall be adequate for the intended current and voltage. Splices made in such cables shall provide continuity of all components.