30 CFR 77.805
§ 77.805 Cable couplers and connection boxes; minimum design requirements.
United States · 30 CFR — Mineral Resources · Status: effective
Cite this
- Citation
- 30 CFR 77.805, § 77.805 Cable couplers and connection boxes; minimum design requirements, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/134104
- Permanent ID
ys:prov:134104@1- SHA-256
e504053d824f4f71d55dcb00143f19a879e7db65709f81c75826e5ddece2d071
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a)(1) Couplers that are used in medium- or high-voltage power circuits shall be of the three-phase type and enclosed in a full metallic shell, except that the Secretary may permit, under such guidelines as he may prescribe, no less effective couplers constructed of materials other than metal.
(2) Cable couplers shall be adequate for the intended current and voltage.
(3) Cable couplers with any metal exposed shall be grounded to the ground conductor in the cable.
(4) Couplers shall be constructed to cause the ground check continuity conductor to break first and the ground conductor last when being uncoupled when pilot check circuits are used.
(b) Cable connection boxes shall be of substantial construction and designed to guard all energized parts from personal contact.
Legislative history
This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.