30 CFR 77.901
§ 77.901 Protection of low- and medium-voltage three-phase circuits.
United States · 30 CFR — Mineral Resources · Status: effective
Cite this
- Citation
- 30 CFR 77.901, § 77.901 Protection of low- and medium-voltage three-phase circuits, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/134118
- Permanent ID
ys:prov:134118@1- SHA-256
9c18417e9cfac0d12bb5e8caa9598859828dee224aada686af471a0662734f2b
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) Low- and medium-voltage circuits supplying power to portable or mobile three-phase alternating equipment shall contain:
(1) Either a direct or derived neutral grounded through a suitable resistor at the power source;
(2) A grounding circuit originating at the grounded side of the grounding resistor which extends along with the power conductors and serves as a grounding conductor for the frames of all the electric equipment supplied power from the circuit.
(b) Grounding resistors, where required, shall be of an ohmic value which limits the ground fault current to no more than 25 amperes. Such grounding resistors shall be rated for maximum fault current continuously and provide insulation from ground for a voltage equal to the phase-to-phase voltage of the system.
(c) Low- and medium-voltage circuits supplying power to three-phase alternating current stationary electric equipment shall comply with the National Electric Code.
Legislative history
This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.