§ 77.902 Low- and medium-voltage ground check monitor circuits.
United States · 30 CFR — Mineral Resources · Status: effective
Cite this
- Citation
- 30 CFR 77.902, § 77.902 Low- and medium-voltage ground check monitor circuits, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/134120
- Permanent ID
ys:prov:134120@1- SHA-256
e9ad72c27e3736203113faa6c56a0c16f539cdb28fc10c455ea2ead972aa5cc7
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
On and after September 30, 1971, three-phase low- and medium-voltage resistance grounded systems to portable and mobile equipment shall include a fail safe ground check circuit or other no less effective device approved by the Secretary to monitor continuously the grounding circuit to assure continuity. The fail safe ground check circuit shall cause the circuit breaker to open when either the ground or pilot check wire is broken. Cable couplers shall be constructed to cause the ground check continuity conductor to break first and the ground conductor last when being uncoupled when pilot check circuits are used.