30 CFR 77.1108-1
§ 77.1108-1 Type and capacity of firefighting equipment.
United States · 30 CFR — Mineral Resources · Status: effective
Cite this
- Citation
- 30 CFR 77.1108-1, § 77.1108-1 Type and capacity of firefighting equipment, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/134154
- Permanent ID
ys:prov:134154@1- SHA-256
b101ec3372d7a00fb852fc51e3b804feb3c88db7cff8d45bed6ffd4322f32dab
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
Firefighting equipment required under this § 77.1108 shall meet the following minimum requirements:
(a) Waterlines. Waterlines shall be capable of delivering 50 gallons of water a minute at a nozzle pressure of 50 pounds per square inch. Where storage tanks are used as a source of water supply, the tanks shall be of 1,000-gallon capacity for each 1,000 tons of coal processed (average) per shift.
(b) Fire extinguishers. Fire extinguishers shall be:
(1) Of the appropriate type for the particular fire hazard involved;
(2) Adequate in number and size for the particular fire hazard involved;
(3) Replaced immediately with fully charged extinguishers after any discharge is made from an extinguisher; and
(4) Approved by the Underwriter's Laboratories, Inc., or the Factory Mutual Research Corp., or other competent testing agency acceptable to the Mine Safety and Health Administration.
(c) Fire hose. Fire hose and couplings shall meet the requirements of the Underwriter's Laboratories, Inc., or Factory Mutual Research Corp.'s specifications. Cotton or cotton-polyester jacketed hose shall be treated in accordance with the U.S. Department of Agriculture Forest Service Specification 182 for mildew resistance. The water pressure at the hose nozzle shall not be excessively high so as to present a hazard to the nozzle operator.
Legislative history
This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.