yourstate.us
Mass. Gen. Laws ch. 111, § 72C

Convalescent or nursing homes; lighting and ventilation

Massachusetts · Massachusetts General Laws Chapter 111 — Public Health · Status: effective

Get this as JSONEmbed this
Cite this
Citation
Mass. Gen. Laws ch. 111, § 72C, Convalescent or nursing homes; lighting and ventilation, Massachusetts, version 1 as recorded 2026-09-28, yourstate.us, https://yourstate.us/provision/1549952
Permanent ID
ys:prov:1549952@1
SHA-256
222b3f51b7480b2510a0e3e91ee8b6ddb43a2ffef766649d285ac104b48ec5e7

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

Section 72C. All convalescent or nursing homes shall be provided throughout with electric lighting, and shall have an emergency lighting system for the boiler room, exits, stairs, patient corridors and nurses' stations, which shall be maintained in proper working order and kept available for use when required, and an emergency generator or battery with a capacity sufficient to supply the emergency lighting system for a period of at least one and one half hours, and for such further period as may be determined by rule or regulation of the department. Lighting of not less than five foot candles shall be provided during the night in all corridors and toilets, and lighting of not less than one foot candle shall be provided during the night in patients' rooms. All rooms or other areas used by patients shall, unless lights are kept on therein continuously, have light switches so located as to be within easy reach of wheel chair patients. The use of candles, kerosene lamps or lanterns or other open flame methods of illumination in a convalescent or nursing home is prohibited. All convalescent or nursing homes shall provide each room and space therein which does not have an outside window and which is used by patients or personnel of such home with forced or other ventilation sufficient to change the air therein at least once in six minutes. The department shall make such rules and regulations as may be necessary to carry out the provisions of this section, and shall establish standards of lighting for convalescent or nursing homes, said standards to be in accordance with the lighting levels of the Illuminating Engineering Society.