40 CFR 60.5180
§ 60.5180 Do the emission limits, emission standards, and operating limits apply during periods of startup, shutdown, and malfunction?
United States · 40 CFR — Protection of Environment · Status: effective
Cite this
- Citation
- 40 CFR 60.5180, § 60.5180 Do the emission limits, emission standards, and operating limits apply during periods of startup, shutdown, and malfunction?, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/173097
- Permanent ID
ys:prov:173097@1- SHA-256
6d6791a900f57f98c8334b8aafc0aa0a8522b4f97a1e2a8cb8dfe312396781b5
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
The emission limits and standards apply at all times and during periods of malfunction. The operating limits apply at all times that sewage sludge is in the combustion chamber (i.e., until the sewage sludge feed to the combustor has been cut off for a period of time not less than the sewage sludge incineration residence time). For determining compliance with the CO concentration limit using CO CEMS, the correction to 7 percent oxygen does not apply during periods of startup or shutdown. Use the measured CO concentration without correcting for oxygen concentration in averaging with other CO concentrations (corrected to 7 percent O2) to determine the 24-hour average value.
Legislative history