yourstate.us
40 CFR 60.6565

§ 60.6565 What is the minimum amount of monitoring data I must collect with my continuous parameter monitoring systems?

United States · 40 CFR — Protection of Environment · Status: effective

Get this as JSONEmbed this
Cite this
Citation
40 CFR 60.6565, § 60.6565 What is the minimum amount of monitoring data I must collect with my continuous parameter monitoring systems?, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/173534
Permanent ID
ys:prov:173534@1
SHA-256
3b8fc87de187f4c149eeefff885471e173bcf756e72b6955f01822caeaa60ef6

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) Where continuous parameter monitoring systems are used, obtain 1-hour arithmetic averages for all the following three parameters: (1) Load level of the municipal waste combustor. (2) Temperature of the flue gases at the inlet of your particulate matter control device. (3) Carbon feed rate if activated carbon is used to control dioxins/furans or mercury emissions. (b) Obtain at least two data points per hour in order to calculate a valid 1-hour arithmetic average. (c) Obtain valid 1-hour arithmetic averages for at least 75 percent of the operating hours per day for 90 percent of the operating days per calendar quarter.

Legislative history

This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.