40 CFR 62.14595
§ 62.14595 What are the operator training and qualification requirements?
United States · 40 CFR — Protection of Environment · Status: effective
Cite this
- Citation
- 40 CFR 62.14595, § 62.14595 What are the operator training and qualification requirements?, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/174608
- Permanent ID
ys:prov:174608@1- SHA-256
ee15481b8c126f3f508b389714762c0545d08d5e6b3331ecde2343d2555d40e8
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) You must have a fully trained and qualified CISWI unit operator accessible at all times when the unit is in operation, either at your facility or able to be at your facility within one hour. The trained and qualified CISWI unit operator may operate the CISWI unit directly or be the direct supervisor of one or more other plant personnel who operate the unit. If all qualified CISWI unit operators are temporarily not accessible, you must follow the procedures in § 62.14625.
(b) Operator training and qualification must be obtained through a State-approved program or by completing the requirements included in paragraph (c) of this section.
(c) Training must be obtained by completing an incinerator operator training course that includes, at a minimum, the three elements described in paragraphs (c)(1) through (3) of this section.
(1) Training on the thirteen subjects listed in paragraphs (c)(1)(i) through (xiii) of this section.
(i) Environmental concerns, including types of emissions.
(ii) Basic combustion principles, including products of combustion.
(iii) Operation of the specific type of incinerator to be used by the operator, including proper startup, waste charging, and shutdown procedures.
(iv) Combustion controls and monitoring.
(v) Operation of air pollution control equipment and factors affecting performance (where applicable).
(vi) Inspection and maintenance of the incinerator and air pollution control devices.
(vii) Actions to correct malfunctions or conditions that may lead to malfunction.
(viii) Bottom and fly ash characteristics and handling procedures.
(ix) Applicable Federal, State, and local regulations, including Occupational Safety and Health Administration workplace standards.
(x) Pollution prevention.
(xi) Waste management practices.
(xii) Recordkeeping requirements.
(xiii) Methods to continuously monitor CISWI unit and air pollution control device operating parameters and monitoring equipment calibration procedures (where applicable).
(2) An examination designed and administered by the instructor.
(3) Written material covering the training course topics that can serve as reference material following completion of the course.
Legislative history
This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.