§ 267.191 What are the required design and construction standards for new tank systems or components?
United States · 40 CFR — Protection of Environment · Status: effective
Cite this
- Citation
- 40 CFR 267.191, § 267.191 What are the required design and construction standards for new tank systems or components?, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/186186
- Permanent ID
ys:prov:186186@1- SHA-256
c662295d3f4c63d5d73de5b975550238a17687701717666e1d3254b53200f4e8
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
You must ensure that the foundation, structural support, seams, connections, and pressure controls (if applicable) are adequately designed and that the tank system has sufficient structural strength, compatibility with the waste(s) to be stored or treated, and corrosion protection to ensure that it will not collapse, rupture, or fail. You must obtain a written assessment, reviewed and certified by an independent, qualified registered professional engineer, following 40 CFR 270.11(d), attesting that the tank system has sufficient structural integrity and is acceptable for the storing and treating of hazardous waste. This assessment must include, at a minimum, the following information:
(a) Design standard(s) for the construction of tank(s) and/or the ancillary equipment.
(b) Hazardous characteristics of the waste(s) to be handled.
(c) For new tank systems or components in which the external shell of a metal tank or any external metal component of the tank system will be in contact with the soil or with water, a determination by a corrosion expert of:
(1) Factors affecting the potential for corrosion, such as:
(i) Soil moisture content.
(ii) Soil pH.
(iii) Soil sulfides level.
(iv) Soil resistivity.
(v) Structure to soil potential.
(vi) Existence of stray electric current.
(vii) Existing corrosion-protection measures (for example, coating, cathodic protection).
(2) The type and degree of external corrosion protection needed to ensure the integrity of the tank system during the use of the tank system or component, consisting of one or more of the following:
(i) Corrosion-resistant materials of construction such as special alloys, fiberglass reinforced plastic, etc.
(ii) Corrosion-resistant coating (such as epoxy, fiberglass, etc.) with cathodic protection (for example, impressed current or sacrificial anodes) and
(iii) Electrical isolation devices such as insulating joints, flanges, etc.
(d) Design considerations to ensure that:
(1) Tank foundations will maintain the load of a full tank.
(2) Tank systems will be anchored to prevent flotation or dislodgment where the tank system is placed in a saturated zone, or is located within a seismic fault zone subject to the standards of § 267.18(a).
(3) Tank systems will withstand the effects of frost heave.
Legislative history
This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.