§ 267.196 What are the required devices for secondary containment and what are their design, operating and installation requirements?

United States · 40 CFR — Protection of Environment · Status: effective

Get this as JSONEmbed this
Cite this
Citation
40 CFR 267.196, § 267.196 What are the required devices for secondary containment and what are their design, operating and installation requirements?, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/186191
Permanent ID
ys:prov:186191@1
SHA-256
780e89da6a3b78a953f2c40241026d26adb016734d3fd6094a2a7b09fce14557

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) Secondary containment for tanks must include one or more of the following: (1) A liner (external to the tank). (2) A double-walled tank. (3) An equivalent device; you must maintain documentation of equivalency at the facility. (b) External liner systems must be: (1) Designed or operated to contain 100 percent of the capacity of the largest tank within its boundary. (2) Designed or operated to prevent run-on or infiltration of precipitation into the secondary containment system unless the collection system has sufficient excess capacity to contain run-on or infiltration. The additional capacity must be sufficient to contain precipitation from a 25-year, 24-hour rainfall event. (3) Free of cracks or gaps. (4) Designed and installed to surround the tank completely and to cover all surrounding earth likely to come into contact with the waste if the waste is released from the tank(s) (that is, capable of preventing lateral as well as vertical migration of the waste). (c) Double-walled tanks must be: (1) Designed as an integral structure (that is, an inner tank completely enveloped within an outer shell) so that any release from the inner tank is contained by the outer shell. (2) Protected, if constructed of metal, from both corrosion of the primary tank interior and of the external surface of the outer shell. (3) Provided with a built-in continuous leak detection system capable of detecting a release within 24 hours.