46 CFR 28.855
§ 28.855 Electrical distribution systems.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 28.855, § 28.855 Electrical distribution systems, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/224027
- Permanent ID
ys:prov:224027@1- SHA-256
4e522f05f75dae77e09035c7101b879c2eb8568986ee48a889c1b33e206518b7
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) Each electrical distribution system which has a neutral bus or conductor must have the neutral bus or conductor grounded.
(b) A grounded electrical distribution system must have only one connection to ground. This ground connection must be at the switchboard.