§ 32.56-45 Draft stops—T/ALL.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 32.56-45, § 32.56-45 Draft stops—T/ALL, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/224277
Permanent ID
ys:prov:224277@1
SHA-256
a6f2953337b785b19f76fead1fddf9e1047c8fcf89ffe0c7202b0ae6524d26cf

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) Where ceilings or linings are fitted in accommodation, service, or control spaces, “B” Class bulkheads, except those that form passageways, may stop at the ceiling or lining if draft stops of “B” Class construction are fitted between the ceiling or lining and the deck or shell at intervals of 14 meters (45 feet) or less. (b) Spaces behind the linings of stairways and other trunks must have draft stops at each deck.