§ 35.10-15 Emergency lighting and power systems—T/ALL.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 35.10-15, § 35.10-15 Emergency lighting and power systems—T/ALL, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/224439
- Permanent ID
ys:prov:224439@1- SHA-256
73d6fe37ed815f2f5aabb0e6aaeb0bd6c1f60462b9f74a60fb97a57be85c2c0e
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) Where fitted, it is the duty of the Master to see that the emergency lighting and power systems are tested and inspected at least once in each week that the vessel is navigated to be assured that the system is in proper operating condition.
(b) Internal combustion engine driven emergency generators must be tested under load for at least 2 hours, at least once in each month that the vessel is navigated.
(c) Storage batteries for emergency lighting and power systems must be tested at least once in each 6-month period that the vessel is navigated to demonstrate the ability of the storage battery to supply the emergency loads for the period of time specified in table 112.05-5(a) of this subchapter.
(d) The date of the tests required by this section and the condition and performance of the apparatus must be noted in the vessel's official logbook or in logs or records considered to take the place of the official logbook.