46 CFR 56.50-103

§ 56.50-103 Fixed oxygen-acetylene distribution piping.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 56.50-103, § 56.50-103 Fixed oxygen-acetylene distribution piping, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/225117
Permanent ID
ys:prov:225117@1
SHA-256
3f2a4fd8adb12f1b938ca1a0a8437dcadef30f5bbcaa2d018892c5897deeb3c8

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) This section applies to fixed piping installed for the distribution of oxygen and acetylene carried in cylinders as vessels stores. (b) The distribution piping must include a means, located as close to the supply cylinders as possible, of regulating the discharge pressure from the supply cylinders. (c) Acetylene distribution piping and pipe fittings must be seamless steel. Copper alloys containing less than 65 percent copper may be used in connection with valves, regulators, gages, and other equipment used with acetylene. (d) Oxygen distribution piping and pipe fittings must be seamless steel or copper. (e) When more than two cylinders are connected to a manifold, the supply pipe between each cylinder and manifold must be fitted with a non-return valve. (f) Except for the cylinder manifolds, acetylene is not to be piped at a pressure in excess of 100 kPa (14.7 psig). (g) Pipe joints on the low-pressure side of the regulators must be welded. (h) Branch lines must not run through unventilated spaces or accommodation spaces. (i) Relief valves or rupture discs must be installed as relief devices in the piping system if the maximum design pressure of the piping system can be exceeded. The relief device set pressure must not exceed the maximum design pressure of the piping system. Relief devices must discharge to a location in the weather at least 3 m (10 ft) from sources of ignition or openings to spaces or tanks. (j) Outlet stations are to be provided with suitable protective devices which will prevent the back flow of gas into the supply lines and prevent the passage of flame into the supply lines. (k) Shutoff valves must be fitted at each outlet.

Legislative history

This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.