46 CFR 56.97-38
§ 56.97-38 Initial service leak test (modifies 137.7).
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 56.97-38, § 56.97-38 Initial service leak test (modifies 137.7), United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/225167
- Permanent ID
ys:prov:225167@1- SHA-256
eedce15ec043113c90f08a49cdf6dd924582cebaf4fa1eead204a2c143ed7030
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) An initial service leak test and inspection is acceptable when other types of test are not practical or when leak tightness is conveniently demonstrable due to the nature of the service. One example is piping where shut-off valves are not available for isolating a line. Others may be systems for service water, condensate, plant and instrument air, etc., where checking out of pumps and compressors afford ample opportunity for leak tightness inspection prior to full-scale operation.
(b) The piping system must be gradually brought up to design pressure. After inspection of the piping system has proven that the installation is complete and all joints are leak-tight, the piping has met the requirements of § 56.97-1.