46 CFR 58.16-16

§ 58.16-16 Reducing regulators.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 58.16-16, § 58.16-16 Reducing regulators, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/225223
Permanent ID
ys:prov:225223@1
SHA-256
f27892ade5ca150469720b270c74fec7a9e035eece230f91aed40a01991bee13

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) All systems shall be provided with a regulating device so adjusted as to release gas to the distribution tubing at a pressure not in excess of 18 inches water column, or approximately 10.5 ounces per square inch. (b) The low-pressure side of all regulators must be protected against excessive pressure by means of a suitable relief valve, which must be integral with the regulator. The relief valve must be set to start to discharge at a pressure not less than two times and not more than three times the delivery pressure. (c) All reducing regulators must be fitted with a pressure gage located on the high-pressure side of the regulator.