§ 61.30-10 Hydrostatic test.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 61.30-10, § 61.30-10 Hydrostatic test, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/225335
- Permanent ID
ys:prov:225335@1- SHA-256
766b36f48c8d5161d6b96dbe9aa6f3a43dd0f31ec030fa9dbffb22725a56f092
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
All new installations of thermal fluid heaters must be given a hydrostatic test of 1 1/2 times the maximum allowable working pressure. The test must be conducted in the presence of a marine inspector. No subsequent hydrostatic tests are required unless, in the opinion of the Officer in Charge Marine Inspection, the condition of the heater warrants such a test. Where hydrostatic tests are required, an inspection is made of all accessible parts under pressure. The thermal fluid may be used as the hydrostatic test medium.