§ 63.15-7 Alarms.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 63.15-7, § 63.15-7 Alarms, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/225398
- Permanent ID
ys:prov:225398@1- SHA-256
1c6a67181b3799499b3d592805ad19b8c5c8c4892fac8ba74f79e3d26dff909d
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) An audible alarm must automatically sound when a flame safety system shutdown occurs. A visible indicator must indicate that the shutdown was caused by the flame safety system.
(b) Means must be provided to silence the audible alarm. The visible indicators must require manual reset.
(c) For steam boilers, operation of the lower low water cutoff must automatically sound an audible alarm. A visual indicator must indicate that the shutdown was caused by low water.
(d) For a periodically unattended machinery space, the auxiliary boiler trip alarm required by table 1 to § 62.35-50 of this subchapter satisfies the requirements for the audible alarms specified in this section.