§ 63.25-1 Small automatic auxiliary boilers.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 63.25-1, § 63.25-1 Small automatic auxiliary boilers, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/225403
Permanent ID
ys:prov:225403@1
SHA-256
e926eb63e5aab05311ef4322ae9cd593b231e62b13909e435b2bed7bf2130cc2

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

Small automatic auxiliary boilers defined as having heat-input ratings of 400,000 Btu/hr. or less (117 kilowatts or less) must also meet the following requirements. (a) Small automatic auxiliary boilers must be equipped with a visual indicator which indicates when the low water cutoff has activated. (b) A prepurge period of a sufficient duration to ensure at least four changes of air in the combustion chamber and stack, but not less than 15 seconds must be provided. Ignition must occur only before or simultaneously with the opening of the fuel oil valve.