46 CFR 63.25-5
§ 63.25-5 Fired thermal fluid heaters.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 63.25-5, § 63.25-5 Fired thermal fluid heaters, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/225405
- Permanent ID
ys:prov:225405@1- SHA-256
8b99671b8e64522e04f3c41ad2c91642a9fdacab28f4dec95ad250416648a17b
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) Construction. Fired thermal fluid heaters must meet the requirements of part 52 of this subchapter, as applicable.
(b) Controls. Fired thermal fluid heaters must have a low fluid level cutout device or a low flow device. When the rate of fluid flow through the heating coils is insufficient to ensure proper heat transfer, the device must cut off the fuel supply to the burner. If the fluid temperature exceeds the designed maximum operating temperature, a high temperature limit device must cut off the fuel supply to the burner. These devices must be of the manual reset type.