46 CFR 71.25-20
§ 71.25-20 Fire detection and extinguishing equipment.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 71.25-20, § 71.25-20 Fire detection and extinguishing equipment, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/225802
- Permanent ID
ys:prov:225802@1- SHA-256
f4efe00818dad43fea6fa373dfa5b23548324f2f9b1a9d96bdf1602822b0fcc1
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) At each annual inspection, the inspector must ensure that the following tests and inspections of fire detection and extinguishing equipment have been conducted:
(1) All portable fire extinguishers and semi-portable fire extinguishing systems must be maintained in accordance with NFPA 10, chapter 7 (incorporated by reference, see § 71.25-3). Chapter 7 requires persons performing annual and periodic maintenance, and recharging to be certified. The Coast Guard requires that the servicing persons be properly licensed to perform fire extinguisher maintenance as required by local authorities having jurisdiction. Monthly inspections required by NFPA 10 may be conducted by the owner, operator, person-in-charge, or a designated member of the crew.
Table 71.25-20(a)(1)
(2) Fixed fire extinguishing systems must be checked as noted in table 71.25-20(a)(2). In addition all parts of the fixed fire extinguishing systems must be examined for excessive corrosion and general conditions.
Table 71.25-20(a)(2)
(3) All fire detection and extinguishing systems, all piping controls, valves, and alarms must be checked to ascertain that the system is in operating condition. In this respect, automatic sprinkling systems must be checked by means of test stations or opening heads, smoke detection systems must be checked by introducing smoke into the accumulators, fire detection and manual alarm systems must be checked by test stations or actuating detectors or pull boxes, and steam smothering lines must be checked with at least a 50 p.s.i. air pressure with the ends capped or by blowing steam through the lines at the designed pressure.
(4) The fire main system must be operated and the pressure checked at the most remote and highest outlets. All firehose must be subjected to a test pressure equivalent to the maximum pressure to which they may be subjected in service, but not less than 100 p.s.i.
(b) [Reserved]
Legislative history
This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.