46 CFR 76.17-25
§ 76.17-25 Additional protection required.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 76.17-25, § 76.17-25 Additional protection required, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/225970
- Permanent ID
ys:prov:225970@1- SHA-256
6b7eadf44bcd4cc988677753536835afeeb25863e6cb44550a7724f7584483f8
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) In order that any residual fires above the floor plates may be extinguished when a foam system is installed for the protection of spaces other than tanks, at least 2 fire hydrants, in addition to those required for the machinery space by subpart 76.10, shall be installed outside of the machinery space entrances. Such hydrants shall be fitted with sufficient hose so that any part of the machinery space may be reached with at least 2 streams of water, and each hose shall be equipped with an approved combination nozzle, applicator, and self-cleaning strainer as described in § 76.10-10(j)(3).
(b) [Reserved]