46 CFR 76.30-5
§ 76.30-5 Zoning.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 76.30-5, § 76.30-5 Zoning, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/225998
- Permanent ID
ys:prov:225998@1- SHA-256
bbbd1f0e3b7d89c0460905e899dade62a490233dd00549bfb1095eda63fdcb15
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) The fire detection system must be divided into separate zones to restrict the area covered by any particular alarm signal.
(b) All spaces in a fire detection zone must be accessible from one to another without leaving the deck involved. All doors in watertight subdivision bulkheads and main vertical zone bulkheads must be assumed closed for the purpose of this requirement.
(c) The fire detection zone must not include spaces on more than one deck, except:
(1) Adjacent and communicating spaces on different decks in the ends of the vessel, having a combined deck area of not more than 3,000 feet.
(2) Isolated rooms or lockers in such spaces as mast houses, wheelhouse top, etc., which are easily communicable with the area of the fire-detection circuit to which they are connected.
(d) The fire detection zone must not include more than 50 protected rooms or spaces.
(e) Individual tubing circuits must not contain more than 1,000 feet of pneumatic tubing or its equivalent. However, more than one tubing circuit may be included in the same fire detection zone.
Legislative history
This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.