yourstate.us
46 CFR 76.33-10

§ 76.33-10 Location and spacing of accumulators.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 76.33-10, § 76.33-10 Location and spacing of accumulators, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/226005
Permanent ID
ys:prov:226005@1
SHA-256
8fb72dc1f09c42ffab3e7bcfcfc287539c381da81d7c6483d65ded99946282cf

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) Smoke accumulators must be located overhead in each compartment. Where liable to physical damage, the accumulators and piping must be suitably protected. (b) No spot on the overhead of a protected space may be more than 40 feet from an accumulator. (c) Accumulators must not be located closer to the opening of a ventilator than three times the diameter or equivalent diameter of the opening.

Legislative history

This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.