§ 108.185 Ventilation for enclosed classified locations.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 108.185, § 108.185 Ventilation for enclosed classified locations, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/226756
- Permanent ID
ys:prov:226756@1- SHA-256
e9612ddda04cd41a0fb889f9bfea5b4e6c7966ab16c2b2cdd8a1dd683bcd534e
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) The ventilation system for each enclosed classified location must be designed to maintain a pressure differential between the enclosed classified location and each non-classified location adjacent to the enclosed classified location, so as to prevent the discharge of ignitable gases into the non-classified adjacent locations.
(b) Each air intake must be outside of enclosed classified locations.
(c) Each unit must have alarms that are powered independently of the ventilation motor power and control circuitry and sound at a continuously manned station when—
(1) Gas is present in an enclosed classified location; or
(2) The ventilation system for the space is not working.
(d) Each ventilation system for enclosed classified locations must provide a complete change of air every five minutes.