§ 108.411 Smoke detection system.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 108.411, § 108.411 Smoke detection system, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/226791
- Permanent ID
ys:prov:226791@1- SHA-256
99dab5e04ac272edebfecb68b55faeece21188edbfbac4ca2a217a2b8d7510a2
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
Each smoke accumulator in a smoke detection system must be located on the overhead of the compartment protected by the system in a location—
(a) Where no portion of the overhead of the compartment is more than 12 meters (40 feet) from an accumulator;
(b) That is no closer to the opening of a ventilator than 3 times the diameter or equivalent size of the opening.