§ 108.437 Pipe sizes and discharge rates for enclosed ventilation systems for rotating electrical equipment.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 108.437, § 108.437 Pipe sizes and discharge rates for enclosed ventilation systems for rotating electrical equipment, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/226804
- Permanent ID
ys:prov:226804@1- SHA-256
27c1f79b4391797e3c98026fb1a5e83636ea071960be8f6696f765a3cdc3d25b
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) The minimum pipe size for the initial charge must meet table 108.441 and the discharge of the required amount of CO2 must be completed within 2 minutes.
(b) The minimum pipe size for the delayed discharge must be at least 1.25 centimeters ( 1/2 inch) standard pipe.
(c) The pipe used for the initial discharge must not be used for the delayed discharge, except systems having a volume of less than 57 cubic meters (2,000 cubic feet).