46 CFR 108.463
§ 108.463 Foam rate: Protein.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 108.463, § 108.463 Foam rate: Protein, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/226820
- Permanent ID
ys:prov:226820@1- SHA-256
1b476c97badd1668ab528a6794b87497f3e3616c1c0f26832a5be51019c523bb
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) If the outlets of a protein foam extinguishing system are in a space, the foam rate at each outlet must be at least 6.52 liters per minute for each square meter (.16 gallons per minute for each square foot) of area covered by the systems.
(b) If the outlets of a protein foam extinguishing system are in a tank, the foam rate at each outlet must be at least 4.07 liters per minute for each square meter (.1 gallon per minute for each square foot) of liquid surface in the tank.