§ 111.05-19 Tank vessels; grounded distribution systems.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 111.05-19, § 111.05-19 Tank vessels; grounded distribution systems, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227003
- Permanent ID
ys:prov:227003@1- SHA-256
493651c60cdc0d62517bd82c8fb0a66b65d3e4b70101ab115a39842870d4585c
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) If the voltage of a distribution system is less than 1,000 volts, line to line, a tank vessel must not have a grounded distribution system.
(b) If the voltage of a distribution system on a tank vessel is 1,000 volts or greater, line to line, and the distribution system is grounded (including high-impedance grounding), any resulting current must not flow through a hazardous (classified) location.