46 CFR 111.30-4
§ 111.30-4 Circuit breakers removable from the front.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 111.30-4, § 111.30-4 Circuit breakers removable from the front, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227048
- Permanent ID
ys:prov:227048@1- SHA-256
dd2fb3805f2b56e2c14fbcc48b8e10cd57c112978217dd189441eb6ff2dd2a8d
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
Circuit breakers, when installed on generator or distribution switchboards, must be mounted or arranged in such a manner that the circuit breaker may be removed from the front without unbolting bus or cable connections or deenergizing the supply, unless the switchboard is divided into sections, such that each section is capable of providing power to maintain the vessel in a navigable condition, and meets § 111.30-24 (a) and (b).
Legislative history
This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.