§ 111.30-17 Protection of instrument circuits.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 111.30-17, § 111.30-17 Protection of instrument circuits, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227052
Permanent ID
ys:prov:227052@1
SHA-256
e7530c75d5f96441f2b30ef4ab9b18fcdaef14d9aefb59be81eb5721931c02f1

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) Each circuit that supplies a device on a switchboard, except a circuit under paragraph (b) of this section, must have overcurrent protection. (b) A circuit that supplies a device on a switchboard must not have overload protection if it supplies: (1) An electric propulsion control; (2) A voltage regulator; (3) A ship's service generator circuit breaker tripping control; or (4) A device that creates a hazard to the vessel if deenergized. (c) If short circuit protection is used in any of the circuits listed in paragraph (b) of this section, it must be set at not less than 500% of the expected current. (d) A secondary circuit of a current transformer must not be fused, and the circuit from a current transformer to a device that is not in the switchboard must have a high voltage protector to short the transformer during an open circuit.