46 CFR 111.51-4
§ 111.51-4 Short-circuit calculations for systems 1500 kilowatts or above.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 111.51-4, § 111.51-4 Short-circuit calculations for systems 1500 kilowatts or above, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227086
- Permanent ID
ys:prov:227086@1- SHA-256
8efdf3465eb76e47bb7ae606f584eaea841903356e871dc20f6daf0cfb6ce602
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
Short-circuit calculations must be submitted for systems with an aggregate generating capacity of 1500 kilowatts or more by utilizing one of the following methods:
(a) Exact calculations using actual impedance and reactance values of system components.
(b) Estimated calculations using IEC 61363-1:1998 for AC systems and IEC 61660-1:1997 for DC systems (both incorporated by reference; see § 110.10-1 of this subchapter).
(c) The estimated calculations using a commercially established analysis procedure for utility or industrial applications.