§ 111.75-5 Lighting branch circuits.

United States · 46 CFR — Shipping · Status: effective

Get this as JSONEmbed this
Cite this
Citation
46 CFR 111.75-5, § 111.75-5 Lighting branch circuits, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227122
Permanent ID
ys:prov:227122@1
SHA-256
51d0f787a85fbb78ce3cc22df9ea9d32aa860ecf8499db1649bdae9704c6c6fd

The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.

Full text

(a) Loads. A lighting distribution panel must not supply branch circuits rated at over 30 amperes. (b) Connected load. The connected loads on a lighting branch circuit must not be more than 80 percent of the rating of the overcurrent protective device, computed on the basis of the fixture ratings and in accordance with Section 9.4.2 of IEEE 45.1-2017 (incorporated by reference; see § 110.10-1 of this subchapter). (c) Lighting fixtures on lighting circuits. Each lighting fixture must be on a lighting branch circuit. (d) Overcurrent protection. Each lighting branch circuit must be protected by an overcurrent device rated at 20 amperes or less, except as allowed under paragraph (e) of this section. (e) 25 or 30 ampere lighting branch circuits. Lighting branch circuits rated at 25 and 30 amperes supplying only fixed nonswitched lighting fixtures for cargo hold or deck lighting having only lampholders of the mogul type, or other lampholding devices required for lamps of more than 300 watts, may be supplied by a 30 ampere branch circuit wired with at least No. 10 AWG (5.3 mm 2) conductors if each fixture wire used in wiring each lighting fixture is No. 12 AWG (3.3 mm 2) or larger.

Legislative history

This is a federal regulation, adopted through agency rulemaking under the Administrative Procedure Act — not enacted by a recorded vote of Congress.