§ 111.79-1 Receptacle outlets; general.
United States · 46 CFR — Shipping · Status: effective
Cite this
- Citation
- 46 CFR 111.79-1, § 111.79-1 Receptacle outlets; general, United States, version 1 as recorded 2026-07-09, yourstate.us, https://yourstate.us/provision/227132
- Permanent ID
ys:prov:227132@1- SHA-256
3fead16ca047d58967b7b967747d6d2b2d50e3528a7800ec50b8e7af0eddce63
The hash is SHA-256 of this version's text, with every run of whitespace collapsed to a single space and the ends trimmed. The ID always leads back here, and checking it says whether the text you cited is still the current version.
Full text
(a) There must be a sufficient number of receptacle outlets in the crew accommodations for an adequate level of habitability.
(b) There must be a sufficient number of receptacle outlets throughout the machinery space so that any location can be reached by a portable power cord having a length not greater than 24 meters (75 feet).
(c) Each receptacle outlet must be compatible with the voltage and current of the circuit in which it is installed.
(d) Each receptacle outlet must be suitable for the environment in which it is installed and constructed to the appropriate NEMA or IEC protection standard as referenced in § 111.01-9. Special attention must be given to outlets in hazardous locations.
(e) A receptacle outlet must not have any exposed live parts with the plug opening uncovered.